Best Practice Detail
13-10-0684
Network Operators, Service Providers, Equipment Suppliers, and Property Managers should verify DC fusing levels throughout the power supply and distribution system, especially at the main primary distribution board, to ensure that fuses and breakers are not loaded at more than 80% of their rated ampacity.
Status: Rollover New
References/Comments: Diode OR'ed arrangements require additional special overcurrent protection considerations
Historical events:
- Network Operators
- Service Providers
- Equipment Suppliers
- Property Managers
- Cable
- Internet/Data
- Satellite
- Wireless
- Wireline
- Fire
- Hardware
- Network Operations
- Power
- CSRIC VII: Rollover New In CSRIC VII
