Skip to content
ATIS Best Practices

Best Practice Detail

13-10-0684

Network Operators, Service Providers, Equipment Suppliers, and Property Managers should verify DC fusing levels throughout the power supply and distribution system, especially at the main primary distribution board, to ensure that fuses and breakers are not loaded at more than 80% of their rated ampacity.

Status: Rollover New

References/Comments: Diode OR'ed arrangements require additional special overcurrent protection considerations